Wagner-Smith Equipment Co.

Hi-Pot Adapter

Item Number: Category Search Terms , , , Brand:

For quick, reliable fault detection on underground cables, these units are available for phase-to-phase system voltages upto 35kV. By converting A.C. source voltage to pulsating D.C., these adapters permit testing of cables with a potential level equal to peak source voltage. This field effective method proves especially beneficial for- Testing new cable before initial energizing- Testing repaired cable before re-energizing- Testing suspect cable spans for faults. For metered readout, the Hi-Pot Adapters work in conjunction with CHANCE Phasing Tool No. H1876. A brass male fitting inside the larger end of either adapter simply threads onto the meter probe of the phasing tool. For testing and subsequent discharging, a brass female fitting at the smaller end of the adapter accepts either CHANCE Elbow Adapters or Bushing Adapters for 15 through 35 kV.

  • Illustrated instruction booklet shipped with each Hi-Pot Adapter explains testing and discharging procedures.
  • Units contain high-voltage rectifiers encapsulated in CHANCE orange 1.25 and 1.5 inch diameter Epoxiglas® housings.
Item Number - Category Product Tags , , , Brand:

inquire about this product

Thank you for your interest in this product.

Please utilize this form for product availability, product specifications or additional information. Someone from our team will be in contact with you.

"*" indicates required fields

Name*
We are…
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.
This field is for validation purposes and should be left unchanged.

Wagner-Smith Equipment Co.